Nortec RH2+ Manual de usuario Pagina 10

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 62
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 9
7 | Installation
Location
Mount on a suitable wall or vertical surface. Do not sit the unit on the floor. Allow clearances
required for plumbing and electrical connections. Clearance dimensions shown are for
reference only and are the minimum required for maintenance of the humidifier. Consult local
and national codes before final location and installation. Nortec does not accept responsibility
for installation code violations.
Install only in areas with ambient temperature 41-104°F (5 40°C) relative humidity
5 - 95%.
When possible install below the steam distributor. Take care to provide proper steam line
routing and proper condensate traps.
DO NOT locate the humidifier any further then absolutely necessary from the steam
distributor location as net output will be reduced as a result of heat loss through the steam
line.
When possible, mount the RH2 humidifier at a height convenient for servicing.
Figure 4: Mounting Location / Clearance
Side clearance
for space models
only, see table
36 in. (92 cm)
in. ront learance
duct model
m f c
Additional front clearance
for space models,
see table
24 in.(61 cm)
Min Height
Mount Humidifier
Level
As Close as
Possible to Steam
Distributor
5-95%
Overhead clearance
for space models
only, see table
Humidifier Output lb (kg) Side in. (cm)
<4 (1.8) 12 (30) 12 (30)
6 (2.7) 16 (40) 18 (46)
8 (3.6) 18 (46) 18 (46)
7 ft (2.1 m)
min. Height
for space
models only.
36 (92)
42 (107)
48 (120)
Additional Clearance for Space Models Only
Overhead in. (cm) Front in. (cm)
Note: Do not mount on hot surfaces, where freezing can occur, vibrating surface, or floor.
Vista de pagina 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 61 62

Comentarios a estos manuales

Sin comentarios